Home / IN-D-240-DC-S-G


| Operating Temperature | -20°C to +60°C (Derating >75°C) |
| Storage Temperature | -40°C to +100°C |
| Relative Humidity | 20–90% RH (Non-condensing) |
| Cooling | Convection Cooling |
| Mounting | Back plane / DIN-Rail |
| Enclosure | Cabinet IP42 |
| Dimensions | W: 70mm, H: 130mm, D: 144mm |
| Weight | <1.2Kg Approx. |
| Connectors | Screw Terminals |
| Input | |
|---|---|
| Voltage | 24VDC (18V–36V) |
| Current | 16.5A at Nominal Input 24VDC |
| Isolation |
Input-Case: 500VDC, 30MΩ Input-Output: 500VDC, 30MΩ Output-Case: 500VDC, 30MΩ |
| Input Protection | Reverse polarity and over-current via input fuse |
| Inrush Current | <15A typical |
| Switch On Delay | <100mSec |
| Output | |
| Voltage | 24VDC (±1%) |
| Current | 10.0A |
| Power | 240W |
| Ripple | 150mVp-p (20MHz bandwidth) |
| Ripple Noise | 120mVp-p |
| Line Regulation | ≤1% of Vnom |
| Load Regulation | ≤1% of Vnom (Exclusive OR-ing drop max 0.5VDC) |
| LED Indications | DC Input (Green), DC OK (Green), DC Low/Fault (Red) |
| Output Voltage Adjustment | 22V to 26VDC |
| Protection | Overload, short-circuit, auto-recovery after fault removal |
| Relay Contact | Provided. C, Normally short for OK, open for not OK |
| OR-ing Diode |
Inbuilt for output redundancy and parallel operation Set output voltage equally up to second decimal place |
| Efficiency | >87% from 10% to 100% load (excluding diode and polarity loss) |
| Vibration | 10–55Hz, 19.8m/s² (2G) |
| Safety Standards | UL60950-1 Conformance |
| Switching Frequency | 370KHz |
Model: IN-D-240-DC-S-G
| 1 | Series Name |
| 2 | Type of Mounting |
| 3 | Output Power |
| 4 | Input Type / Voltage |
| 5 | Number of Outputs |
| 6 | Output Voltage |